Eaton UPS 9395 SBM
EATON
The 9395 combines the reliability and redundancy of a multi-module UPS into an integrated, pre-wired solution. With a unique, flexible design that provides scalability, the UPS can adapt to future changes in load demands and new requirements for higher reliability without requiring the purchase of an additional UPS. For example, the 9395 UPS enables you to add a 275 kVA UPM in the field for N+1 redundancy or capacity.
Download Brochure
Technical Specs
UPS output power rating (0,9 p.f.) | |||||||||||
kVA | 225 | 275 | 450 | 550 | 675 | 825 | 900 | 1100 | |||
kW | 204 | 250 | 408 | 500 | 612 | 750 | 816 | 1000 | |||
General | |||||||||||
Efficiency in double conversion mode (full load) | > 94% (According to IEC 62040-3) | ||||||||||
Efficiency in double conversion mode (half load) | > 93% (According to IEC 62040-3) | ||||||||||
VMMS (double conversion) | significantly increased efficiency at low loads | ||||||||||
Efficiency in Energy Saver System (ESS) | up to 99% | ||||||||||
Distributed paralleling with Hot Sync technology | 5 + 1 | ||||||||||
Internal N+1 redundance capable | in 550 : 275 kVA in 825 : 550 kVA in 1100 : 825 kVA |
||||||||||
Field upgradeable | yes | ||||||||||
Inverter/rectifier topology | transformer-free IGBT with PWM | ||||||||||
Audible noise | < 76 dB; < 81 dB (825 and 1100 kVA) | ||||||||||
Altitude (max) | 1000 m without derating (max 2000 m) | ||||||||||
Input | |||||||||||
Input wiring | 3 ph + N + PE | ||||||||||
Nominal voltage rating (configurable) | 220/380, 230/400, 240/415 V 50/60 Hz | ||||||||||
Input voltage range | +15% / -15%, +10% / -10% for bypass | ||||||||||
Input frequency range | 45-65 Hz | ||||||||||
Input power factor | 0,99 | ||||||||||
Input ITHD | < 3-5% on nominal load, depending on the utility UTHD | ||||||||||
Soft start capability | Yes | ||||||||||
Internal backfeed protection | Yes, standard | ||||||||||
Output | |||||||||||
Output wiring | 3 ph + N + PE | ||||||||||
Nominal voltage rating (configurable) | 220/380, 230/400, 240/415 V 50/60 Hz | ||||||||||
Output UTHD | <3% (100% linear load); <5% (reference non linear load) | ||||||||||
Output power factor | 0,9 (e.g. 250 kW at 275 kVA) | ||||||||||
Permitted load power factor | 0,7 lagging - 0,8 leading | ||||||||||
Overload on inverter | 10 min 100-110%; 30 sec 110-125%; 10 sec 125-150%; 300 ms >150% | ||||||||||
Overload when bypass available | Continuous <115%, 20 ms 1000% Note! Bypass fuses may limit the overload capability | ||||||||||
General Characteristics* | |||||||||||
Control panel (LCD) | 10-inch Color Touchscreen with LED panel | ||||||||||
Battery startup | Standard | ||||||||||
Frequency conversion | Standard | ||||||||||
Multi-language | Standard | ||||||||||
Buildings alarm inputs | 5 (galvanic isolated) | ||||||||||
*10-inch display only as an optional feature in 275 and 550 kW products | |||||||||||
Battery | |||||||||||
Type | VRLA, AGM, Gel, Wet Cell (NiCd batteries and flywheel on request) | ||||||||||
Charging method | ABM technology or Float | ||||||||||
Temperature compensation | with EMP | ||||||||||
Battery nominal voltage (lead-acid) | 480 V (40 x 12 V, 240 cells) | ||||||||||
Charging current / Model Default A Max* A |
275 38 83 |
550 76 166 |
825 114 249 |
1100 152 332 |
|||||||
*Limited by maximum UPS input current rating | |||||||||||
Dimension and weights | |||||||||||
225 kVA, 275 kVA | 1350 x 880 x 1880 mm (wxdxh) | 830 kg | |||||||||
225 kVA redundant, 275 kVA redundant |
1890 x 880 x 1880 mm | 1430 kg | |||||||||
450, 500, 550 kVA | 1890 x 880 x 1880 mm | 1430 kg | |||||||||
450, 550 kVA redundant | 2630 x 880 x 1880 mm | 2030 kg | |||||||||
Field upgrade module, 225 or 275 kVA |
740 x 880 x 1880 mm | 600 kg | |||||||||
675, 825 kVA | 3710 x 880 x 1880 mm | 2520 kg | |||||||||
675, 825 kVA + 1 redundant | 4450 x 880 x 1880 mm | 3120 kg | |||||||||
1100 kVA | 4450 x 880 x 1880 mm | 3120 kg | |||||||||
Options – Eaton 9395 SBM | |||||||||||
9395 SBM ratings | |||||||||||
Model | 2000 | 2500 | 3200 | 4000 | 5000 | ||||||
Rating (A) | 2000 | 2500 | 3200 | 4000 | 5000 | ||||||
Dimension and weights | |||||||||||
SBM 2000 | 2200 x 1032 x 1880 mm (wxdxh) | 1400 kg | |||||||||
SBM 2500 | 2200 x 1032 x 1880 mm | 1400 kg | |||||||||
SBM 3200 | 2200 x 1032 x 1880 mm | 1550 kg | |||||||||
SBM 4000 | 2500 x 1032 x 1880 mm | 2400 kg | |||||||||
SBM 5000 | 2500 x 1032 x 1880 mm | 2500 kg | |||||||||
Accessories | |||||||||||
External battery cabinets with long-life batteries, NiCd batteries and flywheel on request, X-Slot connectivity (Web/SNMP, ModBus/Jbus, Relay, Hot Sync, ViewUPS-X remote display), integrated manual bypass for 225-550 kVA | |||||||||||
Communications | |||||||||||
X-Slot | 4 communication bays | ||||||||||
Serial ports | 1 available | ||||||||||
Relay inputs/outputs | 5/1 programmable | ||||||||||
Compliance with standards | |||||||||||
Safety (CB certified) | IEC 62040-1, IEC 60950-1 | ||||||||||
EMC | IEC 62040-2 | ||||||||||
Performance | IEC 62040-3 |
In the interests of continuous product improvement all specifications are subject to change without notice.